TitleProduct

Continuous Emission Monitoring System

  • Price:

    Negotiable

  • minimum:

  • Total supply:

  • Delivery term:

    The date of payment from buyers deliver within days

  • seat:

    Beijing

  • Validity to:

    Long-term effective

  • Last update:

    2020-07-01 20:04

  • Browse the number:

    219

Send an inquiries
+
Xi'an Dingyan Technology Co., Ltd.
Contactaixin:

dykeji(Mr.)  

Email:

telephone:

phone:

Arrea:

Beijing

Address:

No.22, Zaozitai Road, New Industrial Park, High-tech Zone, Xi'an, Shaanxi Province.

Website:

http://www.dycems.com/ http://dykeji.yh-dk.com/

+

Continuous Emission Monitoring System

Continuous Emission Monitoring System is applied to monitor emission of chimney in industrial pollution sources. The measuring components include SO2, NOx, O2, dust, humidity, temperature, pressure, flow velocity,etc.CEMS have obtained CCAEP certification from China Environmental Protection Ministry and a number of technical patents, which is high stable performance.

Applications of system
1.Chimney
2.After the precipitator

3. Channel of chimney entrance

System features
1. Display the real-time monitoring data, transfer data to the client computer and environmental protection department platform simultaneously. Data can be reported, stored, queried, exported, and printed.
2. Adopt high temperature resistant sampling probe and efficient sample gas processing system, low component loss rate.
3. Gas analyzer adopts UV DOAS principle, with fast response speed, strong anti-interference ability, and high measurement accuracy.
4. The system has rich interfaces and strong expandability.
5. On-site installation and technical training from technicians. The overall modular design facilitates maintenance. The technical team can provide remote technical support and on-site guidance.

Spec.

Product

CEMS

Continuous emission monitoring system

Model

DY-FG200

Measuring components

SO2,NOx,O2,dust,etc

temperature,pressure,flow velocity

Measuring range unit

Unit:ppm,mg/m3

Measuring range

SO2,NOx:0~50~100~200~500mg/m3,0~500~1000~2500ppm,

O2:0~25%.

Temp.:0~500℃,humidity:0~40%,pressure:-2.5KPa~+2.5KPa,

Flow:0~40m/s.

Range can be customized

Measuring principle

SO2,NOx:UV DOAS.

Dust:laser backscattering ,O2: electrochemistry

Temperature: thermal resistance

Pressure: metal diaphragm

Velocity: pitot tube differential pressure

Humidity: resistance capacity

Sampling method

extraction

Response time

≤200S

Linearity error

± 2% F.S.

Zero drift

± 2% F.S./24h

Span drift

± 2% F.S./24h

Analog output

4~20mA DC

Digital output

RS232/RS485

Power supply

AC220V+10%,50Hz

Atmospheric pressure

80KPa-106KPa

Purge gas

Instrument-grade compressed air

Environment humidity

≤90%RH

Ambient temperature

-20℃~+50℃

Installation

Ground-mounted

Size

600mm*800mm*2200mm

Explosion-proof

optional


http://www.dycems.com/